7.5   Status Indicators

7.5.1   Not In Auto Indicator

This red lamp flashes continuously when the Off/Manual/Auto switch is not in the Auto position (Figure 7–1).


7.5.2   Shutdown Status Indicator

This red lamp is lit whenever the control detects a Shutdown condition. After the condition has been corrected, the Shutdown indicator can be reset by turning the Off/Manual/Auto switch to the Off (O) position, and pressing the Fault Acknowledge button. The generator set cannot be started when this lamp is on.


7.5.3   Warning Status Indicator

This yellow lamp is lit whenever the control detects a Warning condition. After the condition has been corrected, the Warning indicator can be reset by pressing the Fault Acknowledge button. (It is not necessary to stop the generator set if the fault becomes inactive during generator set operation).