Views: 1243 Author: Site Editor Publish Time: 2020-08-18 Origin: Site
General Features of this unit
Power Capacity Standby Power(50Hz) 520KW / 650KVA
Engine (CCEC Cummins KTA19-G8)
Radiator 40OC max, fans are driven by belt, with
safety guard
24V charge alternator
Alternator: single bearing alternator IP23, insulation
class H/H
Absorber
Dry type air filter, double fuel filter, oil filter, coolant
filter
Main line circuit breaker
Standard control panel
Two12V batteries, rack and cable
Ripple flex exhaust pipe, exhaust siphon, flange,
muffler
User manual
Cummins Standby Generator Set 520KW ENGINE DATA
Manufacturer / Model: CCEC Cummins KTA19-G8, 4-cycle
Air Intake System: Turbo, Water/Air cooling
Fuel System: PT type fuel pump, EFC
Cylinder Arrangement: 6 in line
Displacement: 18.9L
Bore and Stroke: 159*159(mm)
Compression Ratio: 13.9:1
Rated RPM: 1500rpm
Max. Standby Power at Rated RPM: 575KW/782HP
Governor Type: Electronic
Cummins Standby Generator Set 520KW ENGINE DATA Alternator Data
Number of Phase: 3
Connecting Type: 3 Phase and 4 Wires, “Y” type connecting
Number of Bearing: 1
Power Factor: 0.8
Protection Grade: IP23
Altitude: ≤1000m
Exciter Type: Brushless, self-exciting
Insulation Class, Temperature Rise: H/H
Telephone Influence Factor (TIF): <50
THF: <2%
Alternator Capacity: 610KVA
Alternator Efficiencies: 94.90%
GENERATING SET DATA
Voltage Regulation: ≥±5%
Voltage Regulation, Stead State: ≤±1%
Sudden Voltage Warp (100% Sudden Reduce): ≤+25%
Sudden Voltage Warp (Sudden Increase): ≤-20%
Voltage Stable Time (100% Sudden Reduce): ≤6S
Voltage Stable Time (Sudden Increase) ≤6S
Frequency Regulation, Stead State: ≤5%
Frequency Waving: ≤0.5%
Sudden Frequency Warp (100% Sudden Reduce): ≤+12%
Sudden Frequency Warp (Sudden Increase): ≤-10%
Frequency Recovery Time (100% Sudden Reduce): ≤5S
Frequency Recovery
Please conact us for more specification about this unit if you are interested in.